Section 210 71 now requires that meeting rooms of 1 000 square feet or less in other than dwelling units have a minimum number of receptacles.
This new requirement will help serve today s trend that requires we travel with a myriad of electronic devices to meet our daily personal and business needs.
By arium 04 17 2018 graphic representation of new 2017 nec 210 71 meeting room requirements.
Among the 2017 top trends in meeting rooms identified by exhibitor online is wireless connectivity.
In this kafkaesque meeting a mother and her son is fighting a clogged bureaucracy that intensify the personal suffering it is supposed to remedy.
The transition to complete digital conferencing technology solutions eliminates the need for it to attend meetings in case of connection failures and it boosts the overall productivity of meetings.
Here s what you need to know.
The 2017 nec contains a new section that is aimed at providing points of access to electrical power in meeting rooms.
Directed by ellen ugelstad.
Where a room or space is provided with movable partition s each room size shall be determined with the partition.
The 2017 nec now requires meeting rooms measuring 1 000 square feet or less to be equipped with 125 volt 15 or 20 ampere receptacles.
Each meeting room of not more than 93 m 2 1000 ft 2 in other than dwelling units shall have outlets for nonlocking type 125 volt 15 or 20 ampere receptacles the outlets shall be installed in accordance with 210 71 b.
A common directive we hear from clients during the design development phase is that they need electrical receptacles laid out in the space as required by code.